Server Technology PRO4X 36-Outlets PDU

Manufacturer: Legrand Group
Mfr. Part: C4G36RA-2QBE2FE2/30R1

Switched - IEC 208V/60A 2P+G 6Hr - 12 x IEC 60320 C13, 24 x CX - 230 V AC - Branch Circuit, Circuit Protection, Circuit Breaker, Fuse - Network (RJ-45) - 9.84 ft Cord Length - Rack-mountable

Server Technology PRO4X 36-Outlets PDU

About This Product

Overview

Server Technology's PRO4X Switched POPS PDUs run on our state-of-the-art Xerus network interface platform and provide remote access to power, PDU status, input, outlet and branch current monitoring, and outlet on/off control. The PDU features RamLock, a self-locking mechanism to prevent accidental cord disconnects, and our award-winning HDOT Cx outlets that can be deployed as either a C13 or C19. Switched POPS PDUs are secured with strong configurable password, active directory, 256-bit AES encryption, SSH, SSL and HTTPS support. SNMP traps provide automated alerts on power and environmental conditions from Legrand's plug-and-play environmental monitoring sensors like temperature, humidity, water, dry contact closure, airflow, air pressure differential, and more.

  • HDOT Cx Outlets:
  • Cx is the future-ready UL tested hybrid of a C13 and C19 outlet accommodating both C14 and C20 plugs.
  • Network Monitoring:
  • Gain access to valuable data through connections including: HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.
  • Multi-Unit Linking & Cascading:
  • Daisy chain up to 16 PDUs from a primary PDU using a USB or Ethernet connection through a single IP address.
  • Multi-Color LCD:
  • An easy-to-read LCD provides a local indication of power usage, alerts, and alarms.
  • Hot Swappable Controller:
  • The Controller is the PDU's center of intelligence and houses computing, display, and connectivity ports.
  • RamLock Locking Outlets:
  • A mechanical locking mechanism built to secure the broadest range of C14 and C20 plugs in place.
  • Environmental Monitoring:
  • Support up to 12 daisy-chained DX2-series SmartSensors, each with the ability to send SNMP-based alerts and email notifications.
  • Per-Inlet Power Sensing:
  • PIPS® (Per Inlet Power Sensing) Monitors Current Load (A), Voltage (V), Power (W), Apparent Power (VA), Crest Factor, Power Factor, & Energy per inlet.
  • Branch Current Monitoring:
  • Monitors current at each breaker branch and provides SNMP-based alerts and emails on high usage that risks a tripped circuit.
  • Branch Circuit Protection:
  • This PDU meets the UL and IEC 62368-1 requirement for branch circuit protection through UL 489 rated magnetic-hydraulic circuit breakers or UL 248 fuses.

Quick Specifications

Product Series
PRO4X
Product Type
PDU
PDU Type
Switched
Plug/Connector Type
IEC 208V/60A 2P+G 6Hr
Receptacle Type
IEC 60320 C13 CX
Receptacle Detail
12 x IEC 60320 C13 24 x CX
Protection Type
Branch Circuit Circuit Protection Circuit Breaker Fuse
Locking Receptacles
RamLock Locking Outlet