Server Technology Pro4X Smart 36-Outlets PDU

Manufacturer: Legrand Group
Mfr. Part: C4S36RA-U6BD2FE1

Monitored - Universal Input - 12 x IEC 60320 C13, 24 x CX - 230 V AC - Overload Protection, Double Pole, Branch Circuit, Circuit Protection - Network (RJ-45) - 9.84 ft Cord Length - Rack-mountable, Button Mount - Rack

Server Technology Pro4X Smart 36-Outlets PDU

About This Product

Overview

Server Technology's PRO4X Smart PDUs run on our state-of-the-art Xerus network interface platformand provide remote access to power, PDU status, input and branch current monitoring. The PDU features RamLock, a self-locking mechanismto prevent accidental cord disconnects, and our award-winning HDOT Cx outlets that can be deployed as either a C13 or C19. Smart PDUs are secured with strong configurable password, active directory, 256-bit AES encryption, SSH, SSL and HTTPS support. SNMP traps provide automated alerts on power and environmental conditions from Legrand's plug-and-play environmental monitoring sensors like temperature, humidity, water, dry contact closure, airflow, air pressure differential, and more.

  • HDOT Cx Outlets: Cx is the future-ready UL tested hybrid of a C13 and C19 outlet accommodating both C14 and C20 plugs.
  • 4 5 Degree Angled: Inf eed The angled infeed improves accessibility, provides infeed strain relief, and its bend radius is suitable with 60A rated cords.
  • Network Monitoring: Gain access to valuable data through connections including HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.
  • Multi-Unit Linking & Cascading: Daisy chain up to 16 PDUs from a primary PDU using a USB or Ethernet connection through a single IP address.
  • Multi-Color LCD: An easy-to-read LCD provides a local indication of power usage, alerts, and alarms.
  • Hot Swappable Controller: The Controller is the PDU's center of intelligence and houses computing, display, and connectivity ports.
  • Power Quality Measurements: Monitor and alert on the power being fed to the PDU for harmonics, voltage dips and swells, crest factor, and more at the outlet or load.
  • RGB LED Outlet Indicators: RGB LEDs identify an outlet's on/off state, if it's above/below a certain power threshold, or if it's in suspect of a power measurement irregularity. Wa vef o rm Capt ure Capture voltage and current waveforms automatically or upon demand.
  • RamLock Locking Outlets: A mechanical locking mechanism built to secure the broadest range of C14 and C20 plugs in place.
  • Environmental Monitoring: Support up to 12 daisy chained DX2-series SmartSensors, each with the ability to send SNMP-based alerts and email notifications.
  • Per-Inlet Power Sensing: PIPS® (Per Inlet Power Sensing) Monitors Current Load (A), Voltage (V), Power (W), Apparent Power (VA), Crest Factor, Power Factor, & Energy per inlet.
  • Branch Circuit Protection: This PDU meets the UL and IEC 62368-1 requirement for branch circuit protection through UL 489 rated magnetichydraulic circuit breakers or UL 248 fuses.
  • Alternating-Phase Outlets: Evenly distributes multiple phases of power to each outlet for simplified load balancing, reduced cord lengths, and better airflow.
  • HighTemperature Rating: This product has been tested and approved for safe and reliable operation in 60 °C data center environments.
  • Flexible Mounting: Includes standard button mounts along with provisions for custom mounting brackets.
  • Universal Input: A one-size-fits-all universal infeed that accommodates single-phase and three-phase Legrand Universal Input cord options for the same PDU, providing flexibility in rack power deployment.

Quick Specifications

Product Series
Pro4X Smart
Product Type
PDU
PDU Type
Monitored
Phase
Single Phase/Three Phase
Plug/Connector Type
Universal Input
Receptacle Type
IEC 60320 C13 CX
Receptacle Detail
12 x IEC 60320 C13 24 x CX
Protection Type
Overload Protection Double Pole Branch Circuit Circuit Protection